FEC AFC1500 User Manual

Page 79

Advertising
background image

FEC AFC1500 Operations Manual

Chapter 4: System Setup and Wiring (Rev. 6:10/09)

Page 4-35

4.11.2 Considerations for Cable Trolleys

Cables hung by festooning type systems must be secured to the individual cable trolley

and positioned to avoid sharp bends and eliminate or minimize any torsion twisting.

Restraint cords should be used in between cable trolleys to limit movement and reduce

the stress on cables as they are extended. Restraint cord lengths must always be shorter
than the length of cable hung between trolleys.

Cable loops should be consistent in length,typically not exceeding 5 feet in depth between

trolleys. Sufficient number of trolleys should be used in a system to support the entire
length of moving cable and to allow relaxed stacking/festooning of cable loops when tool is
in the retracted position.

One trolley should be fixed to the runway rail to eliminate tugging on or stretching of ca-

bles.

4.11.3 Considerations for Flexible Cable Tracks

Cables must under no circumstances have the opportunity to tangle. Therefore the

clearance height of a track compartment with several similar cables next to one another
must not amount to more that one and a half times the cable diameter.

There should be an “all around” minimum clearance between cables of 10% of the cable’s
diameter.

Cables and hoses with very different diameters should be laid separately. Separation is

achieved by using Flexible Track separators. The following rules should be followed for
cable separation:

o If (Cable 1 Diameter) + (Cable 2 Diameter) > 1.2 x Track Inner Height, then

no separation is necessary.

o

If (Cable 1 Diameter) + (Cable 2 Diameter) ≤ 1.2 x Track Inner Height, then a
horizontal or vertical separator must be used to reduce the inner height,
thereby preventing the entanglement of the cables.

The cable weight should be symmetrically distributed along the width of the track.

Cables must be able to move freely along the radius.

The cables must be secured with strain relief at both ends. In exceptional cases, the ca-

bles may be fixed with strain relief at the moving end only. Unless using a Flexible Cable
Track with integrated strain relief, a gap of 10~30 x cable diameter between the end of the
bending segment and the fixed point is recommended for most cables.

Under no circumstances should excess cable be put into a Flexible Cable Track.

4.11.4 Considerations for Cable Trays & Ladders

Cable drop out panels should be used where cables enter and exit a tray or ladder system.

Sharp bends need to be avoided whenever possible.

Cables should be secured at both entry and exit points of a tray or ladder.

Avoid running high voltage or high frequency cables in the same tray or ladder as signal or

control cables unless cables are designed for such environments.

If excess cable is to be stored in a tray or ladder, do not tightly coil cable. Cable should be

laid in as large of a loop as possible.


Advertising