Distance Control with Load Limit (Method 8)


Upon start of cycle, the press will operate until it achieves [33: Target Distance].
During the press cycle, after achieving [14: Target Load], the press rate will be current
controlled to hold [14: Target Load] until [33: Target Distance] is reached. During the
press cycle, checks are performed for “Interference Check” / “Part Check”, Load and
Distance. If any of these values are compromised, the press will stop and return as
programmed.
(See corresponding sections for Interference Check and Part Check explanations.)






















Load

Distance

[13] Load High Limit

[12] Load Low Limit

[14] Target Load

[31]

Distance

Low Limit

[32]

Distance
High Limit

Final Judgment Zone

[33]

Target

Distance