DSP1500 SAN Unit Operation Manual

PAGE 4-3 (Rev.

4)

Chapter 4: System Setup and Wiring

4.2 SAN Unit Design and Mounting Dimensions

SAN units must be mounted with a minimum clearance of 12mm on each side to allow proper heat
dissipation. Cable connections on the front of the units require 100mm of clearance.
Allow a minimum of 100mm clearance on the bottom of each controller for SAN4 control power
connection and for flash connector hook up when updating firmware.
SAN units must be located a minimum of 600mm from any high transient voltage power source.


Layout SAN Unit(s) to allow proper heat dissipation.
Install fan or cooling device so that the ambient temperature of the SAN Unit does not
exceed 122°F (50°C).
Locate fan to blow directly onto heat sink plate and/or draw heat from top of unit.


Mounting: Top

(1) place

#8-32 screw

Bottom (2) places

#8-32 screw

Weight: SAN3/4-24S, 24HS – 1.4 kg

SAN3/4-40S – 1.8 kg

The diagram shown above shows the dimensions of the SAN3/4-40S.
The protrusion of the heat sink plate (14mm) is on the SAN3/4-40S only, therefore the width of the
SAN3/4-24S & SAN3/4-24HS is 60mm as opposed to 74mm.

SAN3/4-24S, SAN3/4-24HS, SAN3/4-40S