Chapter 4: System Setup and Wiring

4.8.2 Special Configuration Settings (DIP Switch 1~3)

1 ON:

CAL/Zero acceptance window = +/-10% of full scale load.

OFF: CAL/Zero acceptance window = +/-4% of full scale load. (Default)
2 ON:

Parameter changes made by communicating are not saved on EEPROM.

OFF:

Parameter changes made by communicating are saved on EEPROM. (Default)

3 ON: Ramp Up / Down Software Configured (default)

Ramp Up and Ramp Down are set in the User Console Software.

OFF: Ramp Up / Down Hardware Configured (see below)

Ramp Up and Ramp Down are hardware set.

The diagrams below show the effects of the DIP switch 3 setting in the OFF position as seen
on an oscilloscope for a DPT-021R1 press (top diagram) and a DPT-201R3 press (bottom
diagram). Both presses were set up to run Distance Control at maximum speed with the
brake disabled (always disengaged).


















If not used, set DIP switches number 1 and 2 in the OFF position and DIP
switch number 3 in the ON position.

SAN Unit must be powered off and on again for switch changes to take effect.