Yokogawa Multi Channel Oxygen Analyzer System ZR22/AV550G User Manual

Page 35

Advertising
background image

IM 11M12D01-01E

2-16

FOUNDATION Fieldbus communication function

The bi-directional digital communication as standard for FOUNDATION

Fieldbus that is

established by Fieldbus foundation.

Interface : FOUNDATION

Fieldbus H1 (communication speed : 31.25 kb/s)

Physical layer type :

113 (standard-power signaling, bus powered, non I.S.)

Communication line condition:

power supply----9 to 32 VDC, current supply----15 mA (Max)

Signal insulation :

communication terminal to grand terminal, dielectric strength 500 Vrms
(50/60 Hz, 1 min).

Device : Link master

Function block :

AI block :

3 blocks (1 block for each channels)

Transfer the data of averaging oxygen concentration to other instruments.

DI block :

2 blocks

Transfer the status of error and alarm to other instruments.

MAI block

1 block (8 channels)

Transfer the data of oxygen concentration to other instruments.

MAO block

1 block (8 channels)

Import the data of other instruments.

Advertising