1.1.2

System 2

This example, System 2, represents typical applications in large boilers and heating
furnaces, where there is a need to monitor and control oxygen concentration. The
reference gas and calibration-time span gas are (clean, dry) instrument air. Zero gas is
supplied from a gas cylinder.

System 2 uses the ZR40H autocalibration unit, with auto-switching of the calibration
gas. A “combustible gas detected” contact input turns off power to the heater. There’s
also contact output from the converter that can be used to operate a purge gas valve to
supply air to the sensor.

Instrument air

Pressure regulator

Air Set

Needle

valve

flowmeter

Reference gas

Calibration gas

Check valve

~

Zero gas cylinder

ZR40H Auto Calibration unit

Zirconia Oxygen Analyzer, Detector

ZR402G Converter

Calibration gas
unit case

F1.2E.EPS

ZR22S Separate type Explosionproof

Non-hazardous area

Hazardous area

EXA ZR402G

100 to 240 V AC

Contact input

Analog output, contact output
Digital output (HART)

*2

*1

Signal

(6-core shield cable)

Heater (2-core)

*1: Shield cable;

Use shielded signal cables, and connect the shield to the FG terminal of the

converter.

*2: When a zirconia oxygen analyzer is used, 100% N

2

gas cannot be used as the zero

gas. Use approximately 1% of O

2

gas (N

2

-based).

Figure 1.2 System configuration 2