6. Electrical installation

Festo P.BE-CMMD-AS-HW-EN 1002NH

109

6.4.3

Safe stop [X3.1/2]

Pin no.

Designation

Value

Specification

1

24V

24 V DC

24 VDC supply carried out

2

REL

0 V/24 V DC

Setting and resetting the relay for interrupting the driver
supply

3

0V

0 V
[GND 24 V DC *)]

Reference potential for PLC
[Reference potential for the 24V DC power supply and for the
PLC *)]

4

UNASSIGNED

5

NC1

Max. 60 V AC
30 V DC
2 A

Potential-free feedback contact for driver supply,
normally closed contact.

6

NC2

* Reference potential for the 24V DC power supply and for the PLC

Table 6.7 Pin allocation "Safe halt" [X3.1/2]

6.4.4

Field bus CAN [X4]

Pin

Designation

Value

Specification

1

2

CANL

5 V, Ri = 60

CAN-low signal line

3

GND

0 V

CAN-GND, electrically connected to GND
in the controller

4

5

Screening

Connection for the cable screen

6

GND

0 V

CAN-GND, electrically connected to GND
in the controller

7

CANH

5 V, Ri = 60

CAN-high signal line

8

9

Table 6.8 Pin allocation: Field bus CAN [X4]

6.4.5

RS232/RS485 [X5]

Pin

Designation

Value

Specification

1

2

RS232_RxD

10 V, Ri > 2 k

Reception line

3

RS232_ TxD

10 V, Ra < 2 k

Transmission line

4

RS485_A

5

GND

0 V

RS232/485 GND, galvanically connected to GND in
the controller

6

7

8

+5 V_Fuse

5 V

Via PTC on plug

9

RS485_B

Table 6.9 Pin allocation: RS232/RS485 [X5]