Trajectory generator, 6 trajectory generator – Festo Контроллер двигателя CMMD-AS User Manual

Page 57

Advertising
background image

3. Product description

Festo P.BE-CMMD-AS-HW-EN 1002NH

57

Controller

release

START

1

0

1

0

1

0

1

0

1

0

1

0

1

0

Limit switch E0

1

0

DOUT0: READY

DOUT1: MC

DOUT2: ACK

DOUT3: ERROR

Statusword

referenced

1

Limit switch E1

0

1

0

+

STOP

1

0

t1

t1

t1

tx

tx

tx

tx

Drive is moving

t1

= 1.6 ms

tx

= x ms (dependent on ramps)

Fig. 3.6 Signal curve with abort through STOP input

3.7.6

Trajectory generator

With a start signal for a positioning set via DIN8, field bus or RS232
interface, the selected positioning set is loaded into the trajectory generator.
Based on the data record loaded, the necessary internal pre-calculations are made.
The pre-calculations can take from 1.6 to 5 ms. The following configurable options are
available for processing the start signal.

- A start signal detected during an ongoing positioning run is ignored (ignoring).
- After a start signal is detected during an ongoing positioning run, the run

continues to the end (waiting).

- After a start signal is detected, positioning is cancelled and the drive runs

at a constant speed. After pre-calculation is completed, the drive runs to the
new target position (interrupting).

The trajectory generator sends the following messages:

- Target reached, (Default: digital output DOUT1 – MC)
-

Remaining distance reached.