3. Product description

62

Festo P.BE-CMMD-AS-HW-EN 1002NH

Controller

release

START

Intermedicate circuit

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

Holding brake

current-

carrying

1

0

DOUT0: READY

DOUT1: MC

DOUT2: ACK

DOUT3: ERROR

Output stage

release

1

Output stage

switched on

0

Drive is moving

1

0

t1

t1

tx

t1

t1

= 1.6 ms

tx

= x ms (ZK discharges)

Fig. 3.9 Behaviour during interruption of the intermediate circuit supply (error: end stage
off immediately)

Note

The holding brake of the EMMS-AS-…- is not suitable for braking
the motor.

3.7.10 Oscilloscope function

The oscilloscope function implemented in the firmware of the controller is an important
aid to help the commissioning party to optimise the controller settings without using
a separate measuring device. The function allows important signal sequences to be
recorded over time. It consists of three blocks:

- The initialisation section which runs at low priority and performs pre-

calculations for the actual measurement process.

- The data transfer section also has low priority. It is integrated into the time slice

of the serial communication.

- The measuring section runs at a high priority in the rule interrupt and records

the measuring channels. If the trigger condition occurs, the measurement
process is cancelled after a defined number of scan steps.