6. Electrical installation
112
Festo P.BE-CMMD-AS-HW-EN 1002NH
6.4.10 Field bus settings and boot loader
DIP
switches
Significance
1
Node number
2
3
4
5
6
7
8
Bootloader (If the switch is set to ON, the system searches for new firmware on the SD card)
9
Baud rate
10
11
Activation of the CAN interface
12
Terminating resistor
Table 6.15 Assignment of the DIP switches
DIP switches
ON / OFF
Significance
1
ON
DIP switch 1 is the lowest bit, 1011011=91
2
ON
3
OFF
4
ON
5
ON
6
OFF
7
ON
Table 6.16 Sample node number
DIP switches
ON / OFF
Significance
9
ON
DIP switch 9 is the low-order bit,
00=125 kBaud
01=250 kBaud (example)
10=500 kBaud
11=1000 kBaud
10
OFF
Table 6.17 Sample baud rate