Function commands, Setting the operating mode, Example "profile position mode" via rs232 – Festo Контроллер двигателя CMMD-AS User Manual

Page 38

Advertising
background image

3. Product description

38

Festo P.BE-CMMD-AS-HW-EN 1002NH

Function commands

Command

Syntax

Response

Activate controller enable. To do this, the controller
enable logic must be set to "DIN5 and RS232".

OW:0061:00000001 OK! or OW:EEEEEEEE

1)

Deactivate controller enable. To do this, the controller
enable logic must be set to "DIN5 and RS232".

OW:0061:00000002 OK! or OW:EEEEEEEE

1)

Deactivate end stage. To do this, the controller enable
logic must be set to "DIN5 and RS232".

OW:0061:00000003 OK! or OW:EEEEEEEE

1)

Acknowledge error

OW:0030:00010000 OK!

1)

Faulty return values can be called up due to an inappropriately set controller enable logic,

an intermediate circuit that is not loaded, etc.

Table 3.10 Function commands

Setting the operating mode

Due to a necessary synchronization of internal processes, the change of operation mode
can require some cycle times of the controller. We therefore recommend that you always
verify and wait for reception of the desired operation mode.

Operating mode

Syntax

Response

Regulating torque

OW:0030:00000004

OK! or OW:EEEEEEEE

Speed control

OW:0030:00000008

Positioning

OW:0030:00000002

Table 3.11 Operating mode

Faulty return values can be called up due to invalid values that do not come from the
above-named group. The current operation mode can be read by using the "OR"
command.

Example "Profile position mode" via RS232

Note

If you want to perform a positioning, a homing must be performed
once each time the controller is switched on. You can do this via
FCT or as described in chapter "Example "Homing Mode" via
RS232".


With the CAN access simulated via RS232, the motor controller can also be operated in the
CAN "Profile Position Mode". The following describes the sequence in principle.
1. Conversion of the controller enable logic

The controller enable logic can be converted via the COB 6510_10. Since the
simulation of the CAN interface over RS232 can be completely taken over, the enable
logic can also be converted to DINs + CAN.
Command:

=651010:0002

As a result, the release can be granted via the CAN control word (COB 60040_00).
Command:

=604000:0006 Command "Shutdown"

Command:

=604000:0007 Command "Switch on / Disable Operation"

Command:

=604000:000F Command "Enable Operation"