Technical data, General data, Protocol specific data 2.2.1. profibus-dp – Lenze 2130IB User Manual

Page 15: Profibus-fms

Advertising
background image

13

2. Technical data

2.1.

General data

Communication media

RS485

(2130IB.V001)

OFC (SINEC-L2FO)

(2130IB.V002)

Communication profile

PROFIBUS-FMS

(DIN 19245 p1+p2)

PROFIBUS-DP

(DIN 19245 p1+p3)

PROFIBUS participant

Slave

Drive profile

DRIVECOM 21

Baud rate [kBit/s]

93.75, 187.5, 500, 1500

Permissible pollution

Degree of pollution 2 according to
VDE 110 part 2

Permissible humidity

80% relative humidity no condensation

Surge strength to the bus system

250V AC

(2130IB.V001)

infinite

(2130IB.V002)

Ambient temperature

0...45

°C

2.2.

Protocol specific data

2.2.1.

PROFIBUS-DP

Max. number of controllers

31

(without repeater)

122

(with repeater)

Supported services

Data_Exchange, RD_inp, RD_outp,
Slave_Diag, Set_Prm, Chk_Cfg, Get_Cfg,
Global_Control, Set_Slave_add

Functions available as options

Sync, Clear_Data

Maximum PDU length

32 Byte

User data length

12 Byte with DP parameter setting channel
4 Byte w/o DP parameter setting channel

Lenze PNO identification number

0082

hex

Controller master data file for
DIN E 19245 part3
Simatic-S5 COM-ET200/IM 308-B

L_AR0082.GSD
LE0082TD.200

DP parameter setting data

10100000

bin

Configuration data
with DP parameter setting channel

without DP parameter setting channel

B7

hex

(183

dez

),A3

hex

(163

dez

),

93

hex

(147

dez

)

A3

hex

(163

dez

),93

hex

(147

dez

)

2.2.2.

PROFIBUS-FMS

Max. number of controllers

31

(without repeater)

126

(with repeater)

Supported services

Initiate, Abort, Identify, Status, Get-OV-long,
Read, Write

Maximum PDU length

150 Byte

Communication relations

Reference 1: Default Management
Reference 2: MSAC

Advertising