Lenze 2130IB User Manual

Page 61

Advertising
background image

59

Bit

Name

Meaning

11

free 1

For base controllers, mapping to the 4th freely assignable
input
0 = do not activate function
1 = activate function

12

free 2

For 4900/8600controllers, mapping to the 5th freely
assignable input
0 = do not activate function
1 = activate function

13

free 3

For 4900/8600controllers, mapping to the 6th freely
assignable input
0 = do not activate function
1 = activate function

14

free 4

For 4900/8600controllers, mapping to the 7th freely
assignable input
0 = do not activate function
1 = activate function

15

free 5

For 4900/8600controllers, mapping to the 8th freely
assignable input
0 = do not activate function
1 = activate function

1)

only for 4900, 8600 series

Important notes:

If the controller has freely assignable inputs (Lenze codes L-C112
and L-C113), you must not assign the following functions to
terminals when the control is via PROFIBUS (LECOM2).

− Trip reset

(L-C112 = 1..n; L-C113 = 3)

− Ramp function generator
stop

(L-C112 = 1..n; L-C113 = 9)

n = maximum number of
freely assignable inputs

− Ramp function generator
input = 0

(L-C112 = 1..n; L-C113 = 10)

Code L-C112 is the terminal assignment. Code L-C113 determines
the function.

The individual bit control commands of the control word are not
independent of other bit positions. The following table shows which
bits must be assigned to make the desired command effective.

Control state commands

Bits of the control word

15

8

7

0

1 Shutdown

− − − − − − − − − − − − − 1 1 0

2 Switch on

− − − − − − − − − − − − − 1 1 1

3 Operation enabled

− − − − − − − − − − − − 1 1 1 1

4 Disable operation

− − − − − − − − − − − − 0 1 1 1

5 Disable voltage

− − − − − − − − − − − − − − 0

6 Quick stop

− − − − − − − − − − − − − 0 1 −

8 Reset malfunction

− − − − − − − − 0 − − − − − − −
− − − − − − − − 1 − − − − − − −