3.1.4.
DP user data
With PROFIBUS, process data are exchanged cyclically between
master and controller in the user-data phase. In addition to the
process data you can activate a DP parameter setting channel
which will use the first 8 byte of the user data. The data structure is
the same for input and output data, see following tables.
Data structure of user data
Byte
no.
with parameter setting
channel
1
Service
2
Subindex
Parameter setting
3
Index (High-Byte)
channel
4
Index (Low Byte)
5
Data/Error-Byte 1
6
Data/Error-Byte 2
7
Data/Error-Byte 3
8
Data/Error-Byte 4
9
PIW1/POW 1 (High-Byte)
10
PIW1/POW 1 (Low-Byte)
Process data
11
PIW2/POW2 (High-Byte)
12
PIW2/POW2 (Low-Byte)
Byte
no.
without parameter setting
channel
1
PIW1/POW 1 (High-Byte)
2
PIW1/POW 1 (Low-Byte)
Process data
3
PIW2/POW2 (High-Byte)
4
PIW2/POW2 (Low-Byte)