L

24

1.3.1.

Base setting of the drive system

For the base setting, the keypad on the controller or LEMOC2 can be
used.

Setting using the keypad on the controller
1.

Inhibit controller (press STP key).

2.

Set parameter code set (L-C000) to -2-. Now you have access to
the extended parameter set using the keypad.
Confirm the setting using SH + PRG.

3.

Set parameter operating mode (L-C001) to -0- or -1-. Now a
parameter setting is possible via the keypad.
Confirm the setting using SH + PRG.

4.

Enter automation module code (L-C370).
For this, set parameter L-C370 to -1- .
With this setting, the controller recognizes the interface module.
Confirm the setting using SH + PRG.

4a.

Only required for automation module:

Set parameter code set (L-C1000) of the automation module to -2-.
Now you have access to the extended parameter set using the
keypad. Confirm the setting using SH + PRG.

4b.

Only required for automation module:

Enter field bus module code (L-C1120).
For this, set parameter L-C1120 to -3-.
With this setting, the controller recognizes the interface module.
Confirm the setting using SH + PRG.

Note:

After the setting, the operation changes automatically to the code number
which was set last in the base controller (e.g. L-C370), since the
operation re-initializes. This, however, does not influence the parameters
which are already set.

5.

Set the operating mode (L-C001).
This setting determines the write access to the drive parameters.
The following combination is effective:

L-C001

Source of parameter
setting

Source of control (e.g.
set-values)

0

Keypad

Terminal

1

Keypad

Keypad

2

LECOM 1 (LECOM-A/B)

Terminal

3

LECOM 1 (LECOM-A/B)

LECOM 1 (LECOM-A/B)

4

LECOM 2 (PROFIBUS)

Terminal

5

LECOM 2 (PROFIBUS)

LECOM 2 (PROFIBUS)

6

Keypad

LECOM 2 (PROFIBUS)

7

LECOM 1 (LECOM-A/B)

LECOM 2 (PROFIBUS)

For normal operation using PROFIBUS, select 5.
Confirm the setting using SH + PRG.
The read access of LECOM1 (LECOM-A/B) or LECOM2
(PROFIBUS) is possible in any operating mode.