Profibus operating mode – Lenze 2130IB User Manual

Page 36

Advertising
background image

L

34

3.

PROFIBUS operating mode

The PROFIBUS operating mode determines the participants for the
bus system. We distinguish between two operating modes:
• pure PROFIBUS-DP operation
• mixed operation of PROFIBUS-DP and PROFIBUS-FMS
In the following, criteria for the selection of the suitable operating
mode are listed.

Criteria

Code
numbers

Mixed operation
(FS = factory setting)

DP operation
(FS = factory setting)

PROFIBUS-DP master
exists

possible

necessary

PROFIBUS-FMS master
exists

possible

no

Station address can be set

L-C1901

yes
FS = 126

yes
FS = 126

Station address can be set
via bus

no

yes

Baud rate up to 1.5MBaud

L-C1902

yes
FS = 500 kBaud

yes
FS = 500 kBaud

Automatic baud rate
setting

L-C1903

no

possible
FS = active

DP parameter setting
channel

L-C1905

possible
FS = active

possible
FS = active

Data transmission time /
cycle time

medium

low

The PROFIBUS operating mode is selected under L-C1900.

L-C1900

PROFIBUS
operating
mode

-0-

DP operating mode. Only pure PROFIBUS-DP

-1-

Mixed operation. PROFIBUS-FMS and PROFIBUS-
DP services are possible at the same time

The selection of the operating mode causes other bus parameters
to be set automatically to the default values of this operating mode
so that, especially for the DP operating mode, further setttings are
not required.