Data/Error
(4 byte)

Parameter value or fault information in case of an invalid
access. The status of bit service/status determines the meaning
of the data field.

Data
Parameter value which has 1 - 4 bytes, depending on the data
format. Strings or data blocks cannot be transmitted. The data
filed in the Motorola format; i.e. first the High byte/word, then the
low byte/word.
Byte 5

high byte 1

ù high word

ù

Byte 6

low byte 1

ы

ъ

ъ double word

Byte 7

high byte 2

ù low word

ú

Byte 8

low byte 2

ы

ы

Error
Error code. For description see the following table.
Byte 5

Error-Class

Byte 6

Error-Code

Byte 7

ù Additional-Code (high byte)

Byte 8

û Additional-Code (low byte)

Error messages in the Error field (Data/Error):

Error-

Class

Error-

Code

Additional-Code

[hex]

Meaning

6

3

0 0

No access

6

5

1 0

Non-permissible service parameter

6

5

1 1

Invalid subindex

6

5

1 2

Data too long

6

5

1 3

Data too short

6

6

0 0

Object is no parameter

6

7

0 0

Object does not exist

6

8

0 0

Data types are not identical

8

0

0 0

Service cannot be executed

8

0

2 0

Service can currently not be executed

8

0

2 1

Cannot be executed because of local control

8

0

2 2

Cannot be executed because of controller status

8

0

3 0

Out of value range or parameter can only be
changed when controller is inhibited

8

0

3 1

Parameter value too high

8

0

3 2

Parameter value too small

8

0

3 3

Out of range subparameter

8

0

3 4

Value of subparameter too high

8

0

3 5

Value of subparameter too small

8

0

3 6

max. value smaller than min. value

8

0

4 1

Communication object cannot be mapped to
process data

8

0

4 2

Process data length exceeded

8

0

4 3

Collision with other values in general