Status diagram drivecom control – Lenze 2130IB User Manual

Page 58

Advertising
background image

L

56

4.2.2.

Status diagram DRIVECOM control

With LECOM2 control (Lenze parameter L-C001 = 5, 6 or 7), the
Lenze controller has the standardized controller states according to
the DRIVECOM profile.
The information about the momentary controller status (blocks) is
contained in the profile parameter "status word" t or "automation
status word" . Commands in the profile parameter "control word" or
"automation control word" can cause the controller status to
change. These commands are shown by arrows with the
corresponding command numbers in the following figure.

Status diagram DRIVECOM control

NOT READY TO SWITCH ON

Status word xxxx xxxx x0xx 0000

SWITCH ON DISABLED

Status word xxxx xxxx x1xx 0000

automatic when
initializing is completed

READY TO SWITCH ON

Status word xxxx xxxx x01x 0001

Shutdown
xxxx xxxx xxxx x110

SWITCHED ON

Status word xxxx xxxx x01x 0011

Switch on
xxxx xxxx xxxx x111

Enable operation
xxxx xxxx xxxx 1111

Disable operation
xxxx xxxx xxxx 0111

Shutdown
xxxx xxxx xxxx x110

OPERATION ENABLED

xxxx xxxx x01x 0111

Disable voltage
xxxx xxxx xxxx xx0x

Shutdown
xxxx xxxx
xxxx x110

Disable voltage
xxxx xxxx xxxx xx0x

Quick stop
xxxx xxxx xxxx x01x

QUICK STOP ACTIVE

Status word xxxx xxxx x00x 0111

Malfunction

Status word xxxx xxxx x0xx 1000

Disable voltage
xxxx xxxx xxxx xx01

or

quick stop
completed

Malfunction reset
xxxx xxxx 0xxx xxxx

xxxx xxxx 1xxx xxxx

Switch on devices

MALFUNCT. REACT. ACTIVE

Status word xxxx xxxx x0xx 1111

automatic when
malfunction reaction
is completed

9

8

2

10

14

12

6

3

4

5

11

Quick stop
xxxx xxxx xxxx x01x

7

Example: Status.
Information by
parameter 'status word'
(Index 6041hex)
Bit 15 .. Bit 0 (binary)

Example: Command
control commands by
parameter 'control word'
(Index 6040hex)
Bit 15 .. Bit 0 (binary)

Malfunction was
recognized

13

Inhibit ramp generator/Stop ramp generator/Ramp generator zero
QSP terminal