Profibus-dp operating mode – Lenze 2130IB User Manual

Page 37

Advertising
background image

35

3.1. PROFIBUS-DP operating mode

In the following only the settings for pure PROFIBUS-DP operation are
explained.

Settings for the master

Most of the controller manufacturers demand a controller description
file (controller master data file). Therefore, the following files are saved
in the DOS format on the attached diskette:

File name

Meaning

L_AR0082.GSD

Controller master data file according to
DIN E 19245 part 3

LE0082TD.200

Controller master data file (type file) for
Simatic-S5 COM-ET200/IM308-B

The master must be set as follows:

Function

Setting
(depending on the type of master)

Baud rate

500 kBaud (factory setting)
Value as controller parameter
L-C1902 (page 32).

Communication profile
(Bus profile)

PROFIBUS-DP DIN E 19245 part 3
(DP standard)
Value in controller parameter
L-C1901 = 0 (page 32).

Slave station address
(Station number)

126 (factory setting)
Value as controller parameter
L-C1901 (page 32).

DP configuration data (configuration)

with DP parameter setting channel
(L-C1905=1)
(factory setting)

without DP parameter setting channel
(L-C1905=0)

B7

hex

(183

dez

),A3

hex

(163

dez

),

93

hex

(147

dez

)

A3

hex

(163

dez

),93

hex

(147

dez

)

Lenze PNO identification number

0082

hex

DP parameter setting data

10100000

bin

DP user data length

12 byte (with DP parameter setting

channel)

4 byte

(without DP parameter
setting channel)

Setting as controller parameter
L-C1905 (page 32).