4.2.3.

Control word (6040

hex

)

Data format:

Unsigned16

The parameter "control word" is used for the control of the controller. It
contains commands for status changes (see chapter "status diagram
DRIVECOM control" page 56) and other important control commands.

Structure of the parameter "control word":

Bit

Name

Meaning

0

Switch on

Controller states
0 = commands 2,6,8 (controller inhibit)
1 = command 3 (not controller inhibit)

1

Disable voltage

Controller states
0 = commands 7,9,10,12 (controller inhibit)
1 = not command disable voltage

2

Quick stop

Controller states
0 = command 7,10,11 (quick stop)
1 = not command quick stop

3

Operation enabled

Controller states
0 = command 5 (controller inhibit)
1 = command 4 (not controller inhibit)

4

Disable ramp
function generator

Inhibit of ramp function generator.
Quick stop is enabled without the controller leaving its
state.
0 = disable ramp function generator (quick stop)
1 = not disable ramp function generator

5

Stop ramp function
generator

1)

Output of the ramp function generator (speed set-value
integrator) is "frozen".
0 = stop ramp function generator
1 = not stop ramp function generator

6

Ramp function
generator zero

1)

Input of ramp function generator (speed set-value
integrator) is set to zero. Therefore controlled
deceleration along the set ramp.
0 = ramp function generator zero
1 = not ramp function generator zero

7

Reset malfunction

Reset of an error (TRIP). For this, a bit change from 0 to
1 is necessary.

8

reserved

Reserved for DRIVECOM

9

reserved

Reserved for DRIVECOM

10

reserved

Reserved for DRIVECOM