Lenze 2130IB User Manual

Page 21

Advertising
background image

19

Accessories for the wiring of the RS485 connection

Name

Part no.

Explanation

Bus connector
Service designation:
Bus connector PROFIBUS
RS485

363 695

Bus connector for 9-pole SubD socket with
plug terminals to connect the bus cable. Bus
terminal resistor can be added.

Service designation:
Siemens 6ES5 762-1AA12

Cable:
Service designation:
Sinec-L2 bus cable 2-core

Cable resistance
Capacitance per unit length
Loop resistance
Wire diameter
Wire cross-section
Wires
Length

363 677
(sold by
the meter)

135 - 165

Ω/km (f = 3 - 20 MHz)

≤ 30 nF/km
<110

Ω/km

>0.64mm
>0.34qmm
double twisted, insulated and screened
1200m

at 93.75 kBaud

1000m

at 187.50 kBaud

400m

at 500.00 kBaud

200m

at 1500.00 kBaud

Service designation: Siemens SINEC L2 bus
cable (sold by the meter) 6XV1 830-0AH10

• These service designations and technical data of component

manufacturers other than Lenze may not be the latest
information. Therefore they are to be understood as guidelines
only. Precise data can be obtained from the documentation of
these manufacturers.

3.2.2.

2130IB.V002 (OFC)

Communication media

Optical fibre cable (plastic)
HP duplex plug connection

Network topology

Point-to-point (star network when using star couplers)

Number of controllers

1 (per star coupler 15-1, number of star couplers in a
cascade depends on the baud rate)

Minimum cable length

5m

Maximum cable length

25m

OFC wiring
• A star coupler is not necessary for the wiring to a drive

controller (point-to-point connection).

• If you want to connect several controllers, you must use star

couplers.

Accessories for wiring using optical fibre cables are available from the
Siemens SINEC-L2FO products.

Advertising