3.2.2.7.

Read / Write

The Read service is used to read parameters. Either the value or a fault
indication is output.

The Write service is used to write parameters. An acknowledgement or a
fault indication are output .

Lenze controllers support the following fault indications:

Error-

Class

Error-

Code

Additional-Code

[hex]

Meaning

6

3

0 0

No access

6

5

1 0

Non-permissible service parameter

6

5

1 1

Invalid subindex

6

5

1 2

Data too long

6

5

1 3

Data too short

6

6

0 0

Object is no parameter

6

7

0 0

Object does not exist

6

8

0 0

Data types are not identical

8

0

0 0

Service cannot be executed

8

0

2 0

Service can currently not be executed

8

0

2 1

Cannot be executed because of local control

8

0

2 2

Cannot be executed because of controller status

8

0

3 0

Out of value range or parameter can only be
changed when controller is inhibited

8

0

3 1

Parameter value too high

8

0

3 2

Parameter value too small

8

0

3 3

Out of range subparameter

8

0

3 4

Value of subparameter too high

8

0

3 5

Value of subparameter too small

8

0

3 6

max. value smaller than min. value

8

0

4 1

Communication object cannot be mapped to
process data

8

0

4 2

Process data length exceeded

8

0

4 3

Collision with other values in general