2130IB code table

In the following, parameters of the 2130IB module are listed which you
can set via the LECOM1 interface (LECOM-A/B).

The parameters listed in the code table are automatically and
permanently saved.

Explanations:

Code:

Lenze code number of the parameter. Preceeding
zeros may be omitted.

Name:

Name of the parameter

Parameter:

Content or meaning of the parameter values.

Parameters printed in bold show the factory setting.

Code
L-C

Name

Parameter
(Factory setting is printed in bold)

Your
settings

1810

Software
identification

33S2130I_xy000
Software identification of the 2130IB module
x = Software main version
y = Software subversion

1900

PROFIBUS
operating
mode

-0-

DP operation. Only PROFIBUS-DP

-1-

Mixed operation. PROFIBUS-FMS and
PROFIBUS-DP services are possible at the
same time

The operating mode defines the masters which are
able to communicate with the controller. In operating
mode 0 only pure DP masters can be used, and in
operating mode 1 the controller can communicate with
DP or FMS masters.

Data transmission in operating mode 0 is much more
efficient than in operating mode 1.

When changing the operating mode, codes L-C1903
and L-C1904 are also loaded with the corresponding
factory settings.

1901

Station
address

126

1 to 126

Number for precise addressing of the drive in the
PROFIBUS network. This number must only be
assigned once in the bus system.

1902

Baud rate

-2-

93.75 kBaud

-3-

187.5 kBaud

-4-

500.0 kBaud

-6-

1500.0 kBaud

In the bus system, all participants must have the same
baud rate. In the operating mode DP operation
(L-C1900 = 0) and automatic baud rate recognition
(L-C1903 = 1), this code number has no meaning.

1903

Baud rate
recognition

-0-

inactive

(L-C1900 = 0)

-1-

active

(L-C1900 = 1)

Automatic baud rate recognition is only possible in DP
operation; i.e. the drive is set automatically to the baud
rate of the master.