Controller states

Meaning

NOT READY TO SWITCH ON

The controller is being initialized and is not yet
ready to operate. It then switches automaticaly to
the state "switch-on disabled".

SWITCH ON DISABLED

The controller is inhibited (RSP) and waits for
comand 2 (shutdown).

READY TO SWITCH ON

The controller is inhibited (RSP) and waits for
command 3 (switch on).

SWITCHED ON

The controller is inhibited (RSP) and waits for
command 4 (operation enabled)

OPERATION ENABLED

The controller is enabled (RFR). In this state, a
pulse inhibit is possible any time.

MALFUNCTION REACTION
ACTIVE

A fault (TRIP) was recognized and an error
response initiated (e.g. controlled deceleration).

MALFUNCTION

The controller is in a state of error (TRIP).

QUICK STOP ACTIVE

In the state "OPERATION ENABLED" the
command "quick stop" was given. The controller is
decelerated in a controlled way (quick stop ramp).
After deceleration, the controller changes
automatically to "SWITCH ON DISABLED".

Commands

Meaning

COMMAND 2,6,8

(Shutdown)
(CONT-Bit0 = 0)

Command to change from different states to the
state "READY TO SWITCH ON".

COMMAND 3

(Switch on)
(CONT-Bit0 = 1)

Command to change to the state "SWITCHED
ON".

COMMAND 4

(Operation enabled)
(CONT-Bit3 = 1)

Command to change to the state "OPERATION
ENABLED". Controller inhibit is deactivated.

COMMAND 5

(Disable operation)
(CONT-Bit3 = 0)

Command to change to the state "SWITCHED
ON". Controller inhibit is released.

COMMAND 7,9,10,12

(Disable voltage)
(CONT-Bit1 = 0)

Command to change to the state "SWITCH ON
DISABLED". Controller inhibit is released.

COMMAND 7,10,11

(Quick stop)
(CONT-Bit2 = 0)

Command to change to the state "SWITCH ON
DISABLED".
If the controller was enabled, the controller is
decelerated in a controlled way (quick stop ramp).

COMMAND 13

(Malfunction/TRIP)

The controller has recognized an error.
In case of certain faults, a controller deceleration
may be necessary (depending on the controller).
Once completed, the controller changes to the
state "MALFUNCTION".

COMMAND 14

(Reset malfunction/TRIP)
(STEU-Bit7 0->1)

Command to acknowledge a fault. The controller
changes to the state "SWITCH ON DISABLED" if
an error is no longer recognized.