25
6.
To save the setting of L-C001 and L-C370 permanently, set
parameter L-C003 "Save parameter set" to 1 (parameter set 1).
Confirm the setting using SH + PRG.
6a.
Only required for automation module:
To save the setting of the parameter change in the automation
module permanently, save the parameter set (L-C1003 = 1).
Confirm the setting using SH + PRG.
7.
Enable the controller (press SH + STP keys). It may be necessary to
undo other controller inhibit sources (terminal 28, TRIP, L-C40).
Note:
If you activate the function "Load factory setting" at the controller, the
settings described under 1 to 7 are deleted.