Station status_2
(1 byte)

Diagnosis data of the controller part 2
Bit no. Meaning
-----------------------------------------------------------------------------------
0

Controller requests new parameter setting.
0 = no request
1 = request for new parameter setting, e.g. since the
DRIVECOM parameter setting channel was changed.

1

User data status
0 = Controller is able to supply user data
1 = Controller is not able supply user data, because
e.g. initializing between communication module and
controller is not yet finished.

2

fixed on 1

3

Communication monitoring in the controller
0 = inactive
1 = active

4

not used

5

Controller input data 'frozen' (Sync)
0 = input data not frozen
1 = input data frozen

6

reserved

7

Information, if the controller parameter set is inactive
and the controller was removed from the cyclic user
data transfer
0 = parameter setting active
1 = parameter setting inactive

Station status_3
(1 byte)

Diagnosis data of the controller part 3
Bit no. Meaning
-----------------------------------------------------------------------------------
0 - 6

reserved

7

Overflow of diagnosis information
0 = no overflow
1 = overflow

Master_Add
(1 byte)

1 to 126
PROFIBUS station address of the DP master which has set the
controller parameters. If the parameters are not yet set, the
value 255 is returned.

Ident_Number
( 2 byte)

0082

hex

Fixed identification number for Lenze controllers

Ext_Diag_Data_1
(1 byte)

Bit no. Meaning
-----------------------------------------------------------------------------------
0 - 5

fixed value 3

6 - 7

fixed value 0

Ext_Diag_Data_2
(2 byte)

Controller-related diagnosis information. Fault code according to
DRIVECOM profile parameter 603F

hex

.