3.2. Operating mode PROFIBUS mixed operation (FMS/DP)

In the operating mode mixed operation, the controller can be called up by
an FMS master or by a DP master. In the following, only these settings
for PROFIBUS-FMS are explained, since the operation using
PROFIBUS-DP is explained on page 35. Notes about restrictions of DP
functions in the operating mode mixed operation are given on page 34.

Settings of the master

Function

Setting

Communication relation
(Connecting mode)

MSAC
acyclic master-slave connection

Slave-LSAP
(Foreign LSAP)

2

Slave-Password
(Password)

0
no password function

Slave station address
(Foreign L2 address)

126 (factory setting)
Value must be the same as the controller
setting in L-C1901 (page 32).

Maximum PDU length
(Max. PDU length)

150

Baud rate

500 kBaud (factory setting)
Value must be the same as the controller
setting in L-C1902 (page 32).

Settings of the controller

Function

Setting

Station address
L-C1901

126

1 bis 126

Number for precise addressing of the drive
in the PROFIBUS network. This number
can only be assigned once per bus system
(page 32).

Baud rate
L-C1902

-2-

93.75 kBaud

-3-

187.50 kBaud

-4-

500.00 kBaud

-6- 1500.00 kBaud
Baud rate. In the bus system, all
participants must have the same baud rate
(page 32).