3.1.2.

Diagnosis data

The controller supplies the following diagnosis data:

Station status_1
(1 byte)

Diagnosis data of the controller part 1
Bit no. Meaning
-----------------------------------------------------------------------------------
0

Controller available?
0 = controller available
1 = controller not available.

Caution! The other bit information is not
defined.

1

Controller communication status
0 = controller is ready to communicate
1 = controller is not ready to communicate

2

Comparison of configuration data between master and
controller
0 = configuration data identical
1 = configuration data not identical

3

Controller diagnosis
0 = no fault information
1 = fault (TRIP)

4

Invalid service request from the master
0 = no invalid service request
1 = invalid service request

5

Invalid response from the controller
0 = no invalid response
1 = invalid response

6

Status DP parameter setting
(DP service DDLM_Set_Prm)
0 = no fault
1 = fault

7

Information about the source of parameter setting.
0 = parameter setting by the momentary master
1 = parameter setting by another master