Rockwell Automation Publication 750-RM001F-EN-P - February 2012

Chapter 8

Slave Modes for Multi-axis Cascaded Systems

Multi-axis Connections

When configuring a multi-axis system, you need to consider the location of each
safety option in the system. The type of cascaded connections that can be made
are dependent upon the Safety mode configurations of the master and slave safety
options and their positions in the system.

Middle and last units in the cascaded chain may be configured for Automatic
reset. A single reset by the first unit also resets all following units in the chain. If a
fault occurs after the first axis in the cascaded chain, only the subsequent axis
enters the safe state. To reset all axes, you must cycle the SS_In input on the first
axis.

For slave units in a multi-axis system, the SS_In, SLS_In, and DM_In input
signal types (if used) must be configured for output switching signal devices
(OSSD) because the output from the previous unit is also configured for OSSD.

For middle or last units in multi-axis systems, the safety option regards the Door
Monitor input as a Door Control output from an upstream axis, and performs a
logical AND with its internal Door Control signal to form the cascaded Door
Control output.

For information on door control in the master unit, see

Door Control

on

page 67

.

Typical Safety Mode Combinations

Cascaded Connections Allowed

Master Safety Option

First Slave Safety Option

(1)

(Second Safety Option in System)

SS_Out to

SS_In

SLS_Out to

SLS_In

DC_Out to

DM_In

(2)

Safe Stop

Slave - Safe Stop

Yes

Yes

Safe Stop with Door Monitoring

Slave - Safe Stop

Yes

Yes

Safe Limited Speed

Slave - Safe Stop

Yes

Yes

Slave - Safe Limited Speed

Yes

Yes

Yes

Safe Limited Speed with Door Monitoring

Slave - Safe Stop

Yes

Yes

Slave - Safe Limited Speed

Yes

Yes

Yes

Safe Limited Speed with Enabling Switch Monitoring

Slave - Safe Stop

Yes

Yes

Slave - Safe Limited Speed

Yes

Yes

Yes

Safe Limited Speed with Door Monitoring and Enabling
Switch Monitoring

Slave - Safe Stop

Yes

Yes

Slave - Safe Limited Speed

Yes

Yes

Yes

Safe Limited Speed Status Only

Slave - Safe Stop

Yes

Yes

Slave - Safe Limited Speed Status Only

Yes

Yes

(1) P20 [Cascaded Config] parameter equals Cascaded Middle Unit (Multi Mid).
(2) DC_Out to DM_In connections are required only for systems implementing door control or systems monitoring cascaded stopped status.