138

Rockwell Automation Publication 750-RM001F-EN-P - February 2012

Chapter 11

Configuration Examples

Example 1: Door Control Group Settings

Figure 51 - Door Control Group Parameters

Follow these steps to configure Door Control operation for the safety option.

1. From the Door Control group, choose the P57 [Door Out Type]

parameter.

2. Set the P57 [Door Out Type] parameter to 0 (default), which equals

Power to Release (Pwr to Rel).

This setting was chosen because power must be applied to the solenoid
inside the TLS-3 GD2 gate switch to release the gate interlock.

3. Choose the P58 [DM Input] parameter.

The default setting is 0 for applications that do not use an interlock switch.

4. Set the P58 [DM Input] parameter value to 1 for 2NC (dual-channel

equivalent) operation.

In this example application, the DM Input (DM_In) monitors the TLS-3
GD2 switch, which has two normally-closed (2NC) safety contacts.

5. Choose the P59 [Lock Mon Enable] parameter.

The default value is 0 (Disabled) for applications without an interlock
switch.

6. Set the P59 [Lock Mon Enable] parameter value to 1 (Enabled) because

this application uses the TLS-3 GD2 interlock switch.

7. Choose the P60 [Lock Mon Input] parameter.

The default value is 0 (Not Used) for applications that do not use an
interlock switch.

Port 04: Param File-Group

FILE: Parameter Groups

Door Out Type

ESC

AUTO

Not Enabled
0.000 Hz

F

GROUP: Door Control

DM Input
Lock Mon Enable

HIM Screen

Software Screen