Chapter 9

Safe Maximum Speed and Direction Monitoring

Figure 43 - Acceleration Fault When P66 [Max Acc Stop Typ] Set to ‘Use Safe Torque Off with Check
for Standstill (Torque OFF)’

(1) This signal is internal, between the safety option and drive.

For more information about faults, see

Fault Reactions

on

page 155

.

Safe Direction Monitoring
(SDM)

When configured for Safe Direction Monitoring, the safety option monitors the
feedback direction and initiates the configured Safe Stop Type when motion in
the illegal direction is detected. You configure Safe Direction Monitoring by
using the P42 [Direction Mon] parameter. This parameter also determines the
direction, positive or negative, in which motion is allowed.

Table 16 - Enable Safe Direction Monitoring

You may configure a position limit, in encoder units, tolerated in the wrong
direction before a Direction fault occurs, by using the P43 [Direction Tol]
parameter.

Stop Request

Stop Delay

P47 [Max Stop Time]

Acceleration Fault

P66 [Max Acc Stop Typ]

P48 [Standstill Speed]

Speed

Time

Motion Power

(1)

DC_Out

SS_In

SS_Out

P42 [Direction Mon] Parameter

Description

0 = Disabled

Safe Direction Monitoring is disabled.

1 = Positive Always

Safe Direction Monitoring is active any time the configuration is
valid and not Disabled.

2 = Negative Always

3 = Positive During SLS

Safe Direction Monitoring is performed only when the safety
option is actively monitoring Safe Limited Speed.

4 = Negative During SLS

IMPORTANT

Be sure to set the P30 [Fbk 1 Polarity] and P35 [Fbk 2 Polarity] configuration
parameters properly for a consistent direction between encoder 1 and encoder
2.