Rockwell Automation Publication 750-RM001F-EN-P - February 2012

141

Configuration Examples

Chapter 11

Example Application 2

This example application shows how to change the default configuration settings
to set up the safety option for an application with these basic parameters:

Safe Stop (SS) enabled with an E-stop button.
Safe Limited Speed (SLS) initiated with a 2NC contact switch.
A configured Safe Maximum Speed (SMS) limit.
Door Monitoring (DM)
Door Control (DC) to control a guardlocking switch (TLS-3 GD2,

Power to Release style).

A Reset button with 1 NO contact.
Enabling Switch (ESM) with 2NC contacts. Hold the switch in the

middle position to access the machine for maintenance while it is running
at Safe Limited Speed.

One encoder connected with Sin/Cos output signal and resolution of

1024.

Each of the following sections describes the settings you need to enter for each
parameter group. You can use a HIM module, DriveExplorer, DriveExecutive, or
RSLogix 5000 software to configure the safety option.

Example 2: Initial Security Group Settings

Figure 53 - Security Group Parameters

Follow these steps to put the safety option into Program mode for configuration.

1. From the Security group, choose the P5 [Lock State] parameter.

The default value of the Lock State parameter is 0 or unlocked.

2. If the safety option is locked (Lock State parameter value equals 1), set the

P5 [Lock State] parameter value to 0.

If an error occurs, a password has been configured to protect the safety
option configuration.

Port 04: Param File-Group

FILE: Parameter Groups

Password

ESC

AUTO

Not Enabled
0.000 Hz

F

GROUP: Security

Lock State
Operating Mode

HIM Screen

Software Screen