Rockwell Automation Publication 750-RM001F-EN-P - February 2012

45

Speed Monitoring I/O Signals

Chapter 4

Figure 9 - Door Control Cascading Outputs

Only these wiring configurations, shown below, are supported for the Door
Control output.

Figure 10 - Door Control Output Wiring

(1) When wired as a source for a safety input, current is limited to 20 mA per output.
(2) For example, SmartGuard 600 controller, Guard I/O module.

Short-circuits of the output loop to ground or 24V will be detected. For cascaded
outputs, cross loops will also be detected.

The outputs are pulse-tested when the P74 [Door Out Mode] parameter is
configured for pulse-testing.

DM_IN_CH0 DM_IN_CH1

DC_OUT_CH0

DC_OUT_CH1

Safety Option (Master)

Safety Option (Slave)

TB2-51

TB2-52

TB2-S32

TB2-S42

+

-

+

-

+

-

+

-

No

Load

Bi-polar

Load

Single-ended

Load

Door Status 2-Channel

Source

(1)

+24V DC

Door Control

Sourcing Output

Door Control

Sinking Output

+24V DC Common

Load

Load

Input Circuit

Input Circuit

TB2-52

TB2-52

TB2-51

TB2-51

TB2-52

TB2-52

TB2-51

TB2-51

(2)

IMPORTANT

If you disable pulse-testing on this output, the achievable SIL, Category, and PL
ratings of your entire safety system are reduced.