Chapter 11

Configuration Examples

Example 1: Initial Security Group Settings

Figure 46 - Security Group Parameters

Follow these steps to put the safety option into Program mode for configuration.

1. From the Security group, choose the P5 [Lock State] parameter.

The default value of the Lock State parameter is 0 or unlocked.

2. If the safety option is locked (Lock State parameter value equals 1), set the

P5 [Lock State] parameter value to 0.

If an error occurs, a password has been configured to protect the safety
option configuration.

3. Choose the P1 [Password] parameter.

4. Type the password.

5. Choose the P6 [Operating Mode] parameter.

The default value is 0, which equals Program.

6. If the safety option is in Run mode (Operating Mode parameter equals 1),

set the P6 [Operating Mode] parameter to 0 to enable you to enter a new
configuration.

7. If you want to configure a password or change the password, choose the

P13 [New Password] parameter.

The default value is 0. Enter a value from 0…4,294,967,295.

8. Type the new password value.

9. Choose the P17 [Password Command] parameter.

10. Set the P17 [Password Command] parameter value to 1, which equals

Change Password (Change PW).

11. Go to the next section to set the parameters found in the General

parameters group.