Rockwell Automation Publication 750-RM001F-EN-P - February 2012

Chapter 12

Troubleshooting the PowerFlex Safety Option Module

I/O Diagnostic Status Attributes

These attributes are stored in the P69 [IO Diag Status] parameter. Each bit
reflects the present state of I/O signal and is used for diagnostics: 0 = open; 1 =
closed.

Bit

Display Text

0

SS In Ch 0

1

SS In Ch 1

2

SS Out Ch 0

3

SS_Out Ch 1

4

SLS In Ch 0

5

SLS In Ch 1

6

SLS Out Ch 0

7

SLS Out Ch 1

8

ESM In Ch 0

9

ESM In Ch 1

10

DM In Ch 0

11

DM In Ch 1

12

DC Out Ch 0

13

DC Out Ch 1

14

LM In Ch 0

15

LM In Ch 1

16

Reset In

17

Reserved

18

SLS Cmd

19

Stop Cmd

20

MP Out Ch 0

(1)

(1) Refer to

Guard Status Attributes

, bit 2, on page

156

.

21

MP Out Ch 1

Bits 22…31 are Reserved.

IMPORTANT

When the safety option is not in Run mode, the P69 [IO Diag Status] parameter
is not updated.