Safe torque off without standstill checking – Rockwell Automation 21G PowerFlex 750-Series AC Drives Reference Manual User Manual

Page 64

Advertising
background image

64

Rockwell Automation Publication 750-RM001F-EN-P - February 2012

Chapter 6

Safe Stop and Safe Stop with Door Monitoring Modes

Figure 13 - Timing Diagram for Safe Stop 2

(1) This signal is internal, between the safety option and drive.
(2) DC_Out output shown configured as Power to Release. See

Door Control

on

page 67

for more information.

Safe Torque Off without Standstill Checking

When Safe Torque Off without Standstill Checking is initiated, motion power is
removed immediately and the configured Stop Delay P47 [Max Stop Time]
begins. Door control logic is set to Unlock when the Stop Delay P47 [Max Stop
Time] expires, regardless of speed.

Figure 14 - Timing Diagram for Safe Torque Off without Standstill Checking

(1) This signal is internal, between the safety option and drive.
(2) DC_Out output shown configured as Power to Release. See

Door Control

on

page 67

for more information.

SS_Out Output

SS_In Input

Stop Request

Stop Delay: P47

Standstill Position and Standstill

Speed Monitoring

(drive remains enabled)

P51 [Stop Decel Tol]

P48 [Standstill Speed]

Speed

Stop Monitoring Delay:

P46

Time

Motion Power

(1)

Stop Command

(1)

DC_Out Output

(2)

Stop Request

Stop Delay: P47

Safe Torque-off

Active

Door Control
Output Unlock

Time

SS_Out Output

SS_In Input

Speed

Motion Power

(1)

Stop Command

(1)

DC_Out Output

(2)

TIP

All Stop Types require an encoder to be connected.