Rockwell Automation Publication 750-RM001F-EN-P - February 2012

133

Configuration Examples

Chapter 11

Example 1: General Group Settings

Figure 47 - General Group Parameters

Follow these steps to configure the general operation of the safety option.

1. From the General group, choose the P20 [Cascaded Config] parameter.

2. Set the P20 [Cascaded Config] parameter to 0 (default) to configure the

safety option as a Single unit.

3. Choose the P21 [Safety Mode] parameter.

The default setting is 1, which equals Safe Stop.

4. Set the P21 [Safety Mode] parameter value to 4 for Master, Safe Limited

Speed with Door Monitoring mode (Lim Speed DM).

In this mode, the door is locked when the machine speed is above a
configured Safe Speed Limit. The door can be unlocked when the machine
is at Standstill Speed or is at or below the Safe Speed Limit and the SLS_In
input is off.

5. Choose the P22 [Reset Type] parameter.

6. Set the P22 [Reset Type] parameter value to 2 (default), which equals

Manual Monitored (Monitored).

The Manual Monitored setting requires a closing and opening of the reset
circuit for a reset.

7. Choose the P24 [OverSpd Response] parameter.

The default Overspeed Response time is 42 ms.

8. Set the P24 [OverSpd Response] parameter value to 1, which equals 48

ms.

See

Overspeed Response Time

on page

49

for details.

9. Go to the next section to configure the type of feedback by using the

Feedback parameters group.