Speed Monitoring I/O Signals

Chapter 4

Figure 5 - Safety Input Wiring Examples

Table 4 - Safety Option Input Terminals

Short-circuits of the input loop to ground or 24V will be detected. For dual-
channel inputs, cross loops will also be detected.

Test_Out_0 (S11)
Test_Out_1 (S21)

Dual-channel
Equivalent
Safety Device

Dual-channel
Complementary
Safety Device

Single
Channel
Safety Device

Solid State
Safety Device

Safety Option

N/C
N/C

Input 1
Input 0

GND

OSSD2

OSSD1

Safety Option

Safety Option

Safety Option

Input 1
Input 0

Input 1
Input 0

24V_COM (A2)
Input 1
Input 0

Test_Out_0 (S11)
Test_Out_1 (S21)

Test_Out_0 (S11)
Test_Out_1 (S21)

Test_Out_0 (S11)
Test_Out_1 (S21)

2NC or 2 NC 3s

1NC

1NC+1NO or 1NC+1NO 3s

2 OSSD 3s

IMPORTANT

Cross wiring of Test Outputs to Inputs is not allowed. For example, do not
connect TEST_OUT_0 to Input 1 or TEST_OUT_1 to Input 0.

Function

Safe Stop
(SS_In)

Safe
Limited
Speed
(SLS_In)

Door
Monitoring
(DM_In)

Enabling
Switch
Monitoring
(ESM_In)

Lock
Monitoring
(LM_In)

Input 0 = Channel 0

S12

S52

S32

S72

X32

Input 1 = Channel 1

S22

S62

S42

S82

X42