Safety Configuration and Verification

Chapter 10

Resetting the Configuration

When the safety option is unlocked and the P6 [Operating Mode] parameter
equals 0 (Program), you can reset the safety option’s configuration parameters to
their factory default settings, by setting the P7 [Reset Defaults] parameter to 1.
The reset parameters are sent to the safety option when the P6 [Operating Mode]
parameter is changed to 1 (Run).

Basics of Application
Development and Testing

Configuration for the intended SIL CL3, PL e, or Cat 4 system should be carried
out by the system integrator or an operator trained and experienced in safety
applications. The developer must follow good design practices.

Use functional specifications, including flow charts, timing diagrams and

sequence charts.

Perform a configuration review.
Perform configuration validation.