If the Safe Stop Type is initiated or if a Safe Stop is initiated due to a fault, the
SS_Out output is turned OFF.

If an error is detected on either channel of the dual-channel output, a fault occurs.
I/O faults are Stop Category faults, which initiate the configured Safe Stop Type.
The fault is latched until the safety option is successfully reset.

For more information on faults, refer to

Chapter 12

.

Safe Limited Speed Output (SLS_Out)

The safe state for this signal in all cases is OFF.

The SLS_Out output functionality is determined by the configured Safety mode.
If the SLS_In is ON and a successful Safe Stop or Safe Limited Speed reset is
performed, the SLS_Out turns ON in all Safe Limited Speed modes except Safe
Limited Speed Status Only.

For the Safe Limited Speed modes (SLS), the SLS_Out is used to interconnect
speed monitoring safety options in multi-axis applications. For SLS_Out to
SLS_In cascaded signals, the interface is a dual-channel sourcing solid state safety
output connected to a dual-channel safety input configured as OSSD. The
outputs are read back and pulse-tested when the P73 [SLS Out Mode] parameter
is configured for pulse-testing.

For a single unit system or the last unit in a cascaded system, the SLS_Out is
intended to be connected to an input of a safety programmable logic controller
(PLC). The same PLC could also control the Safe Stop function with a safe PLC
output connected to the Safe Stop input (SS_In).

For the first or middle units in a cascaded system, the SLS_Out is intended to be
connected to the Safe Limited Speed input (SLS_In) of the next safety option in
the cascaded system. This lets one SLS switch enable Safe Limited Speed on all
axes at the same time.

IMPORTANT

If you disable pulse-testing on this output, the achievable SIL, Category, and PL
ratings of your entire safety system are reduced.