Safe Limited Speed (SLS) Modes

Chapter 7

Safe Limited Speed with
Door Monitoring Mode

When properly configured for Safe Limited Speed with Door Monitoring, the
safety option performs Safe Limited Speed (SLS) monitoring functions as
described in

Safe Limited Speed (SLS) Mode

on

page 75

in addition to the Safe

Stop functions as described in

Safe Stop Mode

on

page 61

.

In addition, the safety option verifies through monitoring the Door Monitor
input (DM_In) that the safety option controlled by the Door Control output
(DC_Out) is in the expected state. If the door is monitored as opened when it
should be closed, the safety option initiates the configured Safe Stop Type.

The Door Monitor input (DM_In) is ON when the door is closed and OFF
when the door is open. The DM_In input must be ON (door closed) whenever
Safe Limited Speed monitoring is inactive (SLS_In is ON, meaning the circuit is
closed). The DM_In input must also be ON (door closed) during a Safe Limited
Speed Monitoring Delay [LimSpd Mon Delay]. A Door Monitor fault is a Stop
Category fault, which initiates the configured Safe Stop Type.

If Safe Limited Speed Monitoring is active (SLS_In input is OFF) and the safety
option has verified a safe speed condition, the door can be unlocked and opened.

You can monitor the door’s status with or without the door control (lock/
unlock) function. When door control logic is set to lock, it prevents personnel
from entering the hazardous area when the machine is not at a safe speed or at
Standstill Speed.

Figure 20 - Timing Diagram for Safe Limited Speed (SLS) with Door Monitoring Mode

ATTENTION: Make sure that an open door does not result in a hazardous
situation.

If a Safe Stop Type is initiated or a fault occurs while the safety option is actively
monitoring Safe Limited Speed, door control remains unlocked. The safe state of
the SLS_In input may allow the door to be unlocked.

SLS

Request

P55 [Safe Speed Limit]

Speed

Time

SLS Monitoring Delay:

P53

Safe Limited Speed

Active

SLS Fault

Acceptable Speed Range

SLS Request

Removed

Door can be opened.