3. Choose the P1 [Password] parameter.

4. Type the password.

5. Choose the P6 [Operating Mode] parameter.

The default value is 0, which equals Program.

6. If the safety option is in Run mode (Operating Mode parameter equals 1),

set the P6 [Operating Mode] parameter to 0 to enable you to enter a new
configuration.

7. If you want to configure a password or change the password, choose the

P13 [New Password] parameter.

The default value is 0. Enter a value from 0…4,294,967,295.

8. Type the new password value.

9. Choose the P17 [Password Command] parameter.

10. Set the P17 [Password Command] parameter value to 1, which equals

Change Password (Change PW).

11. Go to the next section to set the parameters found in the General

parameters group.

Example 2: General Group Settings

Figure 54 - General Group Parameters

Follow these steps to configure the general operation of the safety option.

1. From the General group, choose the P20 [Cascaded Config] parameter.

2. Set the P20 [Cascaded Config] parameter to 0 (default) to configure the

safety option as a Single unit.

3. Choose the P21 [Safety Mode] parameter.

The default setting is 1, which equals Safe Stop.

Port 04: Param File-Group

FILE: Parameter Groups

Cascaded Config

ESC

AUTO

Not Enabled
0.000 Hz

F

GROUP: General

Safety Mode
Reset Type

HIM Screen

Software Screen