Rockwell Automation Publication 750-RM001F-EN-P - February 2012

93

Safe Limited Speed (SLS) Modes

Chapter 7

SLS Status Only Parameter
List

To configure the safety option for Safe Limited Speed Status Only monitoring,
set these parameters in addition to the Safe Stop parameters listed on

page 69

.

Fil

e

Gr

oup

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta

T

yp

e

HO

ST GROUPS

Gene

ral

21

Safety Mode
Safety Mode
Defines the primary operating mode of the speed monitoring safety functions.

Setting:

7 = “Lim Spd Stat”

RW 8-bit

Integer

Limited S

pe

ed

52

Lim Speed Input
Limited Speed Input
Configuration for Safe Limited Speed input (SLS_In).
“2NC” (1) – Dual-channel equivalent
“2NC 3s” (2) – Dual-channel equivalent 3 s
“1NC+1NO” (3) – Dual-channel complementary
“1NC+1NO 3s” (4) – Dual-channel complementary 3 s
“2 OSSD 3s” (5) – Dual-channel SS equivalent 3 s
“1NC” (6) – Single channel equivalent

Default:
Options:

0 = “Not used”

(1)

0 = “Not used”
1 = “2NC”
2 = “2NC 3s”
3 = “1NC+1NO”
4 = “1NC+1NO 3s”
5 = “2 OSSD 3s”
6 = “1NC”

RW 8-bit

Integer

53

LimSpd Mon Delay
Limited Speed Monitoring Delay
Defines the Safe Limited Speed Monitoring Delay between the SLS_In ON to OFF
transition and the initiation of the Safe Limited Speed (SLS) or Safe Maximum Speed
(SMS) monitoring.

Units:
Default:
Min/Max:

Secs
0
0 / 6553.5

RW 16-bit

Integer

55

Safe Speed Limit
Safe Speed Limit
Defines the speed limit that will be monitored in Safe Limited Speed (SLS) mode.
Units are based on rotary or linear configuration defined by P29 [Fbk 1 Units].

Units:

Default:
Min/Max:

RPM
mm/s
0
0 / 6553.5 RPM
0 / 6553.5 mm/s

RW 16-bit

Integer

56

Speed Hysteresis
Speed Hysteresis
Provides hysteresis for SLS_Out output when Safe Limited Speed monitoring is active.
0% when P21 [Safety Mode] = 1, 2, 3, 4, 5, 6, 8, or 9
10…100% when P21 [Safety Mode] = 7 or 10

Units:
Default:
Min/Max:

%
0
0 / 100

RW 8-bit

Integer

(1) You must configure this parameter with a non-zero value in this mode.