Chapter 8

Slave Modes for Multi-axis Cascaded Systems

Figure 29 - Cascaded Connections

The inputs from the safety switches are monitored by the first safety option,
which is the master. A Safe Limited Speed Reset detected by the first safety
option is cascaded to the subsequent safety options via the SLS_Out to SLS_In
chain. Although all units can be configured for any reset type, we recommend
using automatic reset in all slave units to follow the master units reset type.

Any fault or transition of the SS_In input to OFF is detected by the first safety
option and initiates the configured P45 [Safe Stop Type] to all of the safety
options via the SS_Out to SS_In chain.

Any fault in a slave safety option initiates the configured P45 [Safe Stop Type]
only to that safety option and to slave safety options further down the chain.

Slave, Safe Stop Mode

When properly configured for Slave, Safe Stop mode, the safety option performs
the same functions as Safe Stop except that the safety option regards the Door
Monitor input as a Door Control output from an upstream axis, and performs a
logical AND with its internal Door Control signal to form the cascaded Door
Control output. This makes sure that the Door Control output commands the
door to unlock only if all units command the door to unlock.

Feedback

A2

24V DC

A2

A2

S34 Reset_In

S12 SS_In_0

S22 SS_In_1

S52 SLS_In_0

S62 SLS_In_1

S32 DM_In_0

S42 DM_In_1

S11 Pulse_Source_0
S21 Pulse_Source_1

SS_Out_0 34

SS_Out_1 44

SLS_Out_0 68

DC_Out_0 51

DC_Out_1 52

SLS_Out_1 78

Feedback

X32 LM_In_0

X42 LM_In_1

S34 Reset_In

S12 SS_In_0

S22 SS_In_1

S52 SLS_In_0

S62 SLS_In_1

S32 DM_In_0

S42 DM_In_1

SS_Out_0 34

SS_Out_1 44

SLS_Out_0 68

DC_Out_0 51

DC_Out_1 52

SLS_Out_1 78

S34 Reset_In

S12 SS_In_0

S22 SS_In_1

S52 SLS_In_0

S62 SLS_In_1

S32 DM_In_0

S42 DM_In_1

SS_Out_0 34

SS_Out_1 44

SLS_Out_0 68

DC_Out_0 51

DC_Out_1 52

SLS_Out_1 78

Feedback

12

22

34

11

21

33

A1

A2

42

41

52

51

S72 ESM_In_0

S82 ESM_In_1

Safe Stop Input

Safe Limited Speed Input

Enabling Switch Monitor Input

Manual Reset

First Axis

Feedback

Second Axis

Feedback

Third Axis

Feedback

Middle Axis

(Slave)

Axis 2

First Axis

(Master)

Axis 1

To Door
Control
Solenoid

Auto

Reset

Auto

Reset

Last Axis

(Slave)

Axis 3

Lock Monitor Input

Door Monitor Input

TLS3-GD2

440G-T27260

Power to Release

IMPORTANT

Safe Stop monitoring is not initiated for non-faulted units earlier in the
cascaded chain.

IMPORTANT

The safety reaction time for a cascaded system includes the sum of the reaction
times of each safety option in the chain.