Safety Concept

Chapter 1

Stop Category Definitions

The selection of a stop category for each stop function must be determined by a
risk assessment.

Stop Category 0 is achieved with immediate removal of power to the

actuator, resulting in an uncontrolled coast to stop. Safe Torque Off
accomplishes a Stop Category 0 stop.

Stop Category 1 is achieved with power available to the machine actuators

to achieve the stop. Power is removed from the actuators when the stop is
achieved.

Stop Category 2 is a controlled stop with power available to the machine

actuators. The stop is followed by a holding position under power.

Refer to

Safe Stop Mode

on

page 61

for more information.

IMPORTANT

When designing the machine application, timing and distance should be
considered for a coast to stop (Stop Category 0 or Safe Torque Off). For more
information regarding stop categories, refer to EN 60204-1.