Safe Stop and Safe Stop with Door Monitoring Modes

Chapter 6

Safe Stop 1 and Safe Stop 2

When Safe Stop 1 or 2 is initiated by a transition of the SS_In input from ON to
OFF, the safety option does not initiate the configured Stop Delay P47 [Max
Stop Time] until after the optional Stop Monitoring Delay P46 [Stop Mon
Delay] expires, unless a Stop Category fault occurs during the Stop Monitoring
Delay.

When Safe Stop 1 or 2 is initiated by a Stop Category fault, the Stop Delay P47
[Max Stop Time] begins immediately, regardless of whether a Stop Monitoring
Delay P46 [Stop Mon Delay] is configured.

Deceleration monitoring takes place during the Stop Delay P47 [Max Stop
Time]. These three configurable parameters define the deceleration profile that is
used:

Deceleration Reference Speed, P50 [Decel Ref Speed]
Deceleration Tolerance, P51 [Stop Decel Tol]
Stop Delay, P47 [Max Stop Time]

If Standstill Speed is detected any time after the Safe Stop has been initiated and
before the Stop Delay P47 [Max Stop Time] expires, door control logic is set to
Unlock. If the Standstill Speed is not detected by the end of the configured Stop
Delay P47 [Max Stop Time], a Stop Speed fault occurs. For Safe Stop 1, motion
power is removed when Standstill Speed is reached. For Safe Stop 2, motion
power is not removed.

Figure 12 - Timing Diagram for Safe Stop 1

(1) This signal is internal, between the safety option and drive.
(2) DC_Out output shown configured as Power to Release. See

Door Control

on

page 67

for more information.

Stop Request

Stop Delay: P47

Safe Torque-off

Active

P51 [Stop Decel Tol]

P48 [Standstill Speed]

Speed

Stop Monitoring Delay:

P46

SS_Out Signal

SS_In Signal

Time

Motion Power

(1)

DC_Out Output

(2)

Stop Command

(1)