Speed resolution accuracy for rotary systems – Rockwell Automation 21G PowerFlex 750-Series AC Drives Reference Manual User Manual

Page 50

Advertising
background image

50

Rockwell Automation Publication 750-RM001F-EN-P - February 2012

Chapter 5

General Device and Feedback Monitoring Configuration

Speed Resolution Accuracy for Rotary Systems

Table 5 - Encoder Resolution 16 lines/rev

Table 6 - Encoder Resolution 128 lines/rev

Table 7 - Encoder Resolution 1000 lines/rev

Overspeed Response Time, P24
(OverSpd Response) Setting

Speed (RPM)

1

10

100

1000

10,000

100,000

42

156.253

156.283

156.583

159.583

189.583

489.583

48

78.127

78.142

78.292

79.792

94.792

244.792

60

39.063

39.071

39.146

39.896

47.396

122.396

84

19.532

19.535

19.573

19.948

23.698

61.198

132

9.766

9.768

9.786

9.974

11.849

30.599

228

4.883

4.884

4.893

4.987

5.924

15.299

420

2.441

2.442

2.447

2.493

2.962

7.650

Overspeed Response Time, P24
(OverSpd Response) Setting

Speed (RPM)

1

10

100

1000

10,000

93,750

42

19.535

19.565

19.865

22.865

52.865

332.031

48

9.767

9.782

9.932

11.432

26.432

166.016

60

4.884

4.891

4.966

5.716

13.216

83.008

84

2.442

2.446

2.483

2.858

6.608

41.504

132

1.221

1.223

1.242

1.429

3.304

20.752

228

0.610

0.611

0.621

0.715

1.652

10.376

420

0.305

0.306

0.310

0.357

0.826

5.188

Overspeed Response Time, P24
(OverSpd Response) Setting

Speed (RPM)

1

10

100

1000

10,000

12,000

42

2.503

2.533

2.833

5.833

35.833

42.500

48

1.252

1.267

1.417

2.917

17.917

21.250

60

0.626

0.633

0.708

1.458

8.958

10.625

84

0.313

0.317

0.354

0.729

4.479

5.313

132

0.156

0.158

0.177

0.365

2.240

2.656

228

0.078

0.079

0.089

0.182

1.120

1.328

420

0.039

0.040

0.044

0.091

0.560

0.664