Example 2: stop group settings – Rockwell Automation 21G PowerFlex 750-Series AC Drives Reference Manual User Manual

Page 145

Advertising
background image

Rockwell Automation Publication 750-RM001F-EN-P - February 2012

145

Configuration Examples

Chapter 11

12. Enter 5, 9, or 12V to monitor voltage in accordance with the encoder’s

specifications, or enter 0 (default) to disable encoder voltage monitoring.

13. Choose the P42 [Direction Mon] parameter.

14. Set the P42 [Direction Mon] parameter value to 2, to set up the normal

monitored direction as Negative Always.

15. Choose the P43 [Direction Tol] parameter.

16. Enter value between 0…65,535 degrees based on the encoder’s

specifications.

The default value is 10 degrees.

This sets the position limit tolerated in the wrong direction when Safe
Direction Monitoring is enabled. Entering 360 equals one revolution in
the forward direction before a Direction Fault occurs.

17. Go to the next section to set the parameters found in the Stop parameters

group.

Example 2: Stop Group Settings

Figure 56 - Stop Group Parameters

Follow these steps to configure the Stop operation of the safety option.

1. From the Stop group, choose the P44 [Safe Stop Input] parameter.

2. Set the P44 [Safe Stop Input] parameter value to 1 (default) for 2NC

(dual-channel equivalent) operation.

TIP

The P33 [Fbk 1 Speed] parameter displays the output speed of the encoder as a
value between
-214,748,364.8…214,748,364.8 rpm based on the encoder’s configuration.
You do not need to enter a setting or value for this parameter.

Port 04: Param File-Group

FILE: Parameter Groups

Safe Stop Input

ESC

AUTO

Not Enabled
0.000 Hz

F

GROUP: Stop

Safe Stop Type
Stop Mon Delay

HIM Screen

Software Screen