Installation in frame 8 and larger drives, Terminal connections – Rockwell Automation 21G PowerFlex 750-Series AC Drives Reference Manual User Manual

Page 32

Advertising
background image

32

Rockwell Automation Publication 750-RM001F-EN-P - February 2012

Chapter 3

Installation and Wiring

Installation in Frame 8 and
Larger Drives

When installed in a Frame 8 or larger drive, an EMC Core Kit, catalog number
20-750-EMCSSM1-F8, is required.

Terminal Connections

Shielded cable is required.

Prepare wires for termination on the safety option module with a 6 mm (0.25 in.)
strip length.

Tighten all terminal screws firmly and recheck them after all connections have
been made. Recommended terminal screw torque is 0.2 N•m (1.8 lb•in).

Refer to

page 161

for the I/O signal electrical specifications.

Table 2 - Safety Option Module TB1 Pinouts

Table 3 - Safety Option Module TB2 Pinouts

Terminal

Description

Signal Name

S11

Pulse Test

TEST_OUT_0

S11

Pulse Test

TEST_OUT_0

S11

Pulse Test

TEST_OUT_0

S21

Pulse Test

TEST_OUT_1

S21

Pulse Test

TEST_OUT_1

S21

Pulse Test

TEST_OUT_1

Terminal

Description

Signal Name

S34

Reset Input

RESET_IN

52

Door Control Output

DC_OUT_CH1

51

Door Control Output

DC_OUT_CH0

78

Safe Limited Speed Output

SLS_OUT_CH1

68

Safe Limited Speed Output

SLS_OUT_CH0

44

Safe Stop Output

SS_OUT_CH1

34

Safe Stop Output

SS_OUT_CH0

X42

Lock Monitoring Input

LM_IN_CH1

X32

Lock Monitoring Input

LM_IN_CH0

S42

Door Monitoring Input

DM_IN_CH1

S32

Door Monitoring Input

DM_IN_CH0

S62

Safe Limited Speed Input

SLS_IN_CH1

S52

Safe Limited Speed Input

SLS_IN_CH0

S82

Enabling Switch Monitoring Input

ESM_IN_CH1

S72

Enabling Switch Monitoring Input

ESM_IN_CH0

S22

Safe Stop Input

SS_IN_CH1

S12

Safe Stop Input

SS_IN_CH0

A2

Common, customer supplied

24V_COM

A1

+24V DC, customer supplied

+24V