Output pulse test considerations, Encoder considerations – Rockwell Automation 21G PowerFlex 750-Series AC Drives Reference Manual User Manual

Page 21

Advertising
background image

Rockwell Automation Publication 750-RM001F-EN-P - February 2012

21

Safety Concept

Chapter 1

Output Pulse Test Considerations

If the pulse testing of

any safety output is disabled, the maximum safety rating

will be up to and including SIL CL2, PL d, and CAT 3 for any safety chain
incorporating

any input or output of the safety option.

You may need to disable pulse-testing if the connected device does not support
OSSD inputs. Refer to the product documentation for your connected device.

Encoder Considerations

When configured correctly, the safety option performs these diagnostics on the
encoder:

Sin

2

+ Cos

2

diagnostic

Detection of open or short-circuit
Encoder supply voltage monitoring
Detection of illegal quadrature transitions of the sine and cosine signals

You can use motors that use a single-encoder application if they meet the
following criteria:

Motor is a Permanent magnet (PM) brushless AC motor
Motor controller utilizes the single encoder for control of IGBT firing

(commutation)

Controller is not configured for auto transition to encoderless

commutation in the event of encoder failure

Encoder is of the Sin / Cos type
Motor / Encoder coupling is designed so as to exclude shaft slippage as a

failure mechanism (optional – such as tapered fittings)

IMPORTANT

Setting any of the P72 [SS Out Mode], P73 [SLS Out Mode], or P74 [DC Out
Mode] parameters to 1 = No Pulse Test disables internal diagnostics as well as
external diagnostics required to achieve higher safety ratings.

You must exercise the SS_In input at least once every six months.

Advertising